Yes. Three phase transformers are sometimesnot readily available whereas single phase transformers can generally be found in stock. Three single phase transformers can be used in delta connected primary and wye or delta connected secondary. They should never be connected wye primary to wye secondary, since this will result in unstable secondary voltage. The equivalent three phase capacity when properly connected of three single phase transformers is three times the nameplate rating of each single phase transformer. For example: Three 10 KVA single phase transformers will accommodate a 30 KVA three phase load.
Types of Power Plant (Technology) Natural Gas Based power plant technology Diesel power plant technology Heat Rate of Engine= Fuel Flow or Fuel burned * Fuel Heating Value / Power Output 1 Liter Diesel = 0.85 Kg Example: Heat Rate of Diesel Generator at 100% Load Engine Model- 2506A-E15TAG2 Engine Capacity=400 eKW Fuel Consumption=84 L = 71.4 Kg Electrical Energy Output = 400 KW Heating Value of Diesel = 42.5 MJ/Kg Heat Rate of Engine= Fuel Flow or Fuel burned * Fuel Heating Value / Power Output Heat Rate of Engine = 71.4 Kg * 42.5 MJ/Kg /400KW Heat Rate of Engine =7.58 MJ/KWH Heat Rate of Gas Generator at 100% Load Engine Model- VHP5904LTD Engine Capacity= 900 eKW Fuel Consumption= 271 Nm 3 Electrical Energy Output= 900 KW Fuel Consumption= 0.28 Nm3/KWH Heating Value of Natural Gas= 35.22 MJ/ Nm 3 Heat Rate of Engine= Fuel Flow or Fuel burned * Fue...