Air Compressor Room Ventilation

Ventilation The inlet grids and ventilation fan should be installed in such in way that any recirculation of cooling air to the compressor or dryer is avoided. The maximum air velocity through the grids is 5 m/s or 16.5 ft/s Ventilation system is calculated laws is given bellow Qv= 1.06 N/ D T for Pack versions Qv= Required ventilation capacity in m3/s N= shaft input of compressor in KW D T= Temperature increases in the compressor room in ° C