Lighting Protection system for 23 m or 75 ft height exceeding building

General Information Class II Materials:   Lighting Conductors, air terminals, grounding electrodes and other associated fittings required for the protection of structures exceeding 23m (75 ft) in height. Reference:   NFPA 4.1.1.1 (B)                       Table 4.1.1.1 (B)               NFPA 780 Factory Details Height of the building 80ft or 24.386m m Roof perimeter 358 m NFPA 780 General Requirements: 1.       Air terminals are places at the locations indicated, not more than 2’-0” from the edges of ridges, outside corners, or outside edges of main roofs and must extend a minimum of 24” above object to be protected. 2.       Air terminals are spaced at 50’-0” O.C. Maximum spacing....