Lighting Protection system for 23 m or 75 ft height exceeding building





General Information
Class II Materials: 

Lighting Conductors, air terminals, grounding electrodes and other associated fittings required for the protection of structures exceeding 23m (75 ft) in height.

Reference:  NFPA 4.1.1.1 (B)
                      Table 4.1.1.1 (B)              NFPA 780


Factory Details
Height of the building
80ft or 24.386m m
Roof perimeter
358 m


NFPA 780 General Requirements:
1.      Air terminals are places at the locations indicated, not more than 2’-0” from the edges of ridges, outside corners, or outside edges of main roofs and must extend a minimum of 24” above object to be protected.
2.      Air terminals are spaced at 50’-0” O.C. Maximum spacing.
3.      All structural steel, rebar, framing and miscellaneous steel are made electrically continuous through construction.
4.      Air terminals 24” and over are spaced 25 feet maximum.
5.      One down conductor are provided for every 100 feet perimeter.
6.      Resistance value of earth pit will be measured at any pit below 10 ohm.



Grounds Rods:
a.       Ground rods shall not be less than 12.7 mm (1/2 inch) in diameter and 2.4 m (8 ft ) long.
b.      Ground rods shall be free of paint or other nonconductive coatings.













Material Specification (Class II) For Factory Building
Type of Conductor
Parameter
Copper (Cu)
SI Units
U.S. Units
Air Te4rminal, Solid
Diameter
12.7 mm
½ in.
Main Conductor, Solid Strip
Width
20 mm
0.787 in.
Thickness
3 mm
0.118 in.
Cross-section area
60 mm2
115,000cir.mills
Bonding Conductor Solid strip
Thickness
1.30 mm
0.051 in.
Width
12.7 mm
½ in.




Lighting Risk Index Calculation
Index
Description
Type
Index Number
Index A
Use of Structure
Medium Size Factory
6
Index B
Type of Construction
Reinforced concrete with nonmetal roof
2
Index C
Contents or Consequential Effects
Industrial and agricultural building with especially susceptible contents.
5
Index D
Degree of Isolation
Structure located in an area with a few other structures or trees of similar height.
5
Index E
Type of Terrain
Flat terrain at any level
2
Index F
Height of Structure
24-30 m (24.386m)
11
Index G
Lighting Prevalence
Number of thunderstorm days per year: over 21
21
Building risk Index
51
Marginal Risk index 40
Remarks: Lighting Protection is required



Comments