Can transformers be reverse connected?

Dry type Distribution transformers can be reverse connected without a loss of KVA rating, but there are certain limitations. Transformers rated 1 KVA and larger single phase, 15 KVA and larger three phase can be reverse connected without any adverse affects or loss in KVA capacity. The reason for this limitation in KVA size is, the turns ratio is the same as the voltage ratio.  Example: A transformer with a 480 volt input, 240 volt output - can have the output connected to a 240 volt source and thereby become the primary or input to the transformer, then the original 480 volt primary winding will become the output or 480 volt secondary. On transformers rated below 1 KVA single phase there is a turns ratio compensation on the low voltage winding. This means the low voltage winding has a greater voltage than the nameplate voltage indicates at no load.  For example, a small single phase transformer having a nameplate voltage of 480 volts primary and 240 volts se