Ventilation
The inlet grids and ventilation fan
should be installed in such in way that any recirculation of cooling air to the
compressor or dryer is avoided. The maximum air velocity through the grids is 5
m/s or 16.5 ft/s
Ventilation system is calculated
laws is given bellow
Qv= 1.06 N/DT
for Pack versions
Qv= Required ventilation capacity
in m3/s
N= shaft input of compressor in KW
DT= Temperature increases in the
compressor room in °C