How can you determine the transformer constants referred to the low voltage side if only one set of high voltage measurement is taken?
The process to determine the
transformer constants referred to the low voltage side if only one set of high
voltage measurement is taken , is to short circuit the low voltage side. Then
the watt meter W, a voltage V and an ammeter A are connected in the high voltage
side i.e. primary winding. A low voltage usually 5% to 10% of the rated supply
voltage is applied to the primary and is continuously increase till full load
current will flow both in primary and secondary winding.
As 5% of rated voltage is necessary to
overcome the impedance which is the only limiting component of current flow through each winding. The
impedance is formed by the resistance and reactance of two windings.
Now the total impedance of the transformer
is given by ZT=V1/I1. Where V1 is the applied
voltage and I1 is the rated current. Since flux is directly proportional to
voltage, the mutual flux in the transformer under the short circuit test is
very small. So,the iron or core losses can be neglected and the would exist
only copper losses that can be measured by the watt meter placed in primary
winding. Hence equivalent resistance is given by RT=W/I21
.
Now, equivalent reactance of the
transformer is given by XT2 = Z2T-R2T
Comments
Post a Comment