Problem Solving of Air Dryer
How one solves the problem of Air Dryer?
Condition 1:
Pressure
dew point too high
Fault:
1. Air
inlet temperature too high.
2. Ambient
temperature too high
3. Shortage
of refrigerant
4. Refrigerant
compressor does not run
5. Evaporator
pressure too high
6. Condenser
pressure too high.
Remedy:
1. Check
and correct, if necessary must clean the after cooler of the compressor
2. Check
and correct if necessary draw cooling air via a duct from a cooler place or
relocate the compressor
3. Have
circuit checked for leaks and recharged.
4. Clean
condenser
5. Have
hot gas bypass valve adjusted
6. Clean
condenser and clean the fan
Condition 2:
Condenser
pressure too high or too low
Fault:
1. Fan
control switch out of order
2. Fan
blades or fan motor out of order
3. Ambient
temperature too high
4. Condenser
externally clogged
Remedy:
1. Replace
the fan control switch
2. Check
Fan or Fan motor
3. Check
and correct if necessary draw cooling air via a duct from a cooler place or
relocate the compressor
4. Clean
condenser
Condition 3:
3.1. Compressor Stop or does not start
Fault:
1. Electric
power supply to compressor is interrupted
2. Thermal
protection of refrigerant compressor motor has tripped
Remedy:
1. Check
and correct as necessary by electrician.
2. Motor
will restart when motor windings have cooled down.
Condition
4:
Electronic
condensate drain remains inoperative.
Fault:
Electronic
drain system clogged.
Remedy:
Must
system inspect? Clean the filter automatic drain by opening the manual drain
vlave. Check the functioning of the drain by pushing the test button.
Condition 5:
Condensate
trap continuously discharges air and water
Fault:
Automatic
drain out of order
Remedy:
Check
the system of automatic drain if necessary replace the automatic drain.
Condition
6:
Evaporation
pressure is too high or too low at unload
Fault:
1. Hot
gas valve incorrectly set or out of order
2. Condenser
pressure too high or too low
3. Shortage
of refrigerant.
Remedy:
1. Have
hot gas bypass valve adjusted
2. Clean
condenser
3. Have
circuit checked for leaks and recharged.
Comments