How one does properly Diesel Generator Cooling System Fill?
The system must be
filled properly to prevent air locks. One must air vented during filling from
the engine coolant passages. One must be open the petlock on the aftercooler
for after cool engine. Wait about 2 or 3 minutes to allow air to be vented then
add mixture to bring the level to the top.
Cooling System Fill
The system has design
fill rate of 19 liters = 5 gallon per minute.
One must follow the
caution *** Never use only water for coolant because water create corrosion.
One must use mixture of
50 % water and 50 % propylene glycol or ethylene glycol antifreeze to fill the
cooling system.
Install the pressure
cap.
Operate the engine
until it reaches at temperature of 80 degree Celsius = 180 F
Must check the leaks
for coolant.
One should check the
coolant level again to make certain the system is full of coolant or that the
coolant level has risen to the hot level in the recovery bottle on the system,
if so equipped.