Problem Solving of Air Dryer

Problem Solving of Air Dryer   How one solves the problem of Air Dryer? Condition 1: Pressure dew point too high Fault: 1.       Air inlet temperature too high. 2.       Ambient   temperature too high 3.       Shortage of refrigerant 4.       Refrigerant compressor does not run 5.       Evaporator pressure too high 6.       Condenser pressure too high. Remedy: 1.       Check and correct, if necessary must clean the after cooler of the compressor 2.       Check and correct if necessary draw cooling air via a duct from a cooler place or relocate the compressor 3.       Have circuit checked for leaks and recharged. 4.       Clean condenser 5.       Have ho...

Clarke Fire pump Engine Driveshaft Maintenance

Driveshaft Maintenance: 1.       To service the driveshaft disconnect the negative battery cables, remove the top of guard and set aside. 2.       Rotate engine shaft manually so the U joint grease fittings are Accessible. 3.       Using a held grease gun with N.L.G.I. grade 1 or 2 grease position on grease fitting. Pump with grease until grease is visible at all four cap seals. 4.       Verify all driveshaft connecting bolts tight. 5.       Reinstall top of guard and connect negative cables.

Maintenance Schedule for Clarke Fire Pump Engine

Maintenance Schedule for Clarke Fire Pump Engine Clarke Fire Pump Engine Daily Maintenance: ·          Battery check ·          Lube oil check ·          Radiator water check ·          Cleanliness ·          Fuel Check Clarke Fire Pump Engine Weekly Maintenance: ·          Air cleaner check ·          Battery check ·          Belts check ·          Coolant Hoses check ·          Coolant leaks check ·          Coolant levels and conditions check ·          Coolin...